ABB ACSM1-204 빠른 설치 및 시작 매뉴얼 - 페이지 10
{카테고리_이름} ABB ACSM1-204에 대한 빠른 설치 및 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. ABB ACSM1-204 15 페이지. Regen supply module
ABB ACSM1-204에 대해서도 마찬가지입니다: 매뉴얼 (16 페이지)
10 Quick installation and start-up guide – ACSM1-204
Default connections
Make the following connections on the control unit before attempting to start up the
regen supply module:
• X3:14, 15 Fan control signal. The fan control cable must be connected.
Note: A 24 V DC supply must be connected to the WFU-xx filter.
• X4:8, 9 Thermistor input. The filter temperature monitoring cable must be
connected.
• X6:1, 3 and X6:2, 4 Not in use. Both circuits must be closed with jumpers
(included in delivery).
Connection procedure
The clamp plate can be fastened at the top or the bottom of the JCU Control Unit.
0.7 N·m
(6.2 lbf·in)
Use shrink
tubing or tape to
contain strands
If shielded
cable is in use,
remove outer
jacket of cable
at clamp to
expose cable
shield.
1.5 N·m
(13 lbf·in)