4b) Technical Data
RZ-24-05
Page 07.021.06
Page 07.021.6
4. Information about the RZ-24-05 Central - cont.
Supply voltage
Power consumption
Secondary output voltage
Secondary total load
Operating temperature
Max. number of detectors
Power consumption of the
detection loop
LED indicators
IP rating
IMPORTANT: In total the RZ-24-05 central provides 0.5 A for the supply
of the connected fire detectors, magnets etc.
In case the maximum power consumption is exceeded, the RZ-24-05
will automatically switch off. This also happens when it is overheated!
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20200513
ATTENTION
Some parts inside the casing are
energized with hazardous voltage
during operation! May be opened
only by professionals when being
de-energized (the power supply of
the RZ-24-05 is cut!!)
85 VAC - 264 VAC
about 14 W, own consumption about
40 mA
24 VDC ±10 %
0.5 A (supply of fire detectors, electro-
magnets and other consumers)
0 °C to +40 °C
20
Alarm: I > 12 mA
Interruption: I < 3 mA
Short circuit current: max. 45 mA
Quiescent current: 4.5 mA
Line tension: U
Green LED is on: detection loop is
ready.
Red LED is on: detection loop is
triggered.
Yellow LED is on/flashes: there is a
disturbance.
IP 30
= 20.5...21.4
lin