After configuring the parameters marked with
automatically. It will resume work according to the new parameter value.
NPower and IPower-Plus series support the modification of parameters
marked with
otherwise, the parameter setting will not succeed. IPower does not support
modification of parameters marked with
Rules for battery protection voltage:
A. Over voltage limiting voltage(16.2/32.2/64.4V) ≥ Over voltage
disconnect voltage ≥ Over voltage reconnect voltage +1V.
B. Over voltage reconnect voltage ≥ Low voltage reconnect voltage.
C. Low voltage reconnect voltage ≥ Low voltage disconnect voltage +1V.
D. Low
voltage
voltage(10.5/21/42V).
. Please refer to the following rules for the modification;
disconnect
, the inverter will restart
.
voltage
Low
11
voltage
limiting