Epever MT91 User Manual - Page 15

Browse online or download pdf User Manual for Measuring Instruments Epever MT91. Epever MT91 20 pages. Remote meter

Epever MT91 User Manual
After configuring the parameters marked with
automatically. It will resume work according to the new parameter value.
NPower and IPower-Plus series support the modification of parameters
marked with
otherwise, the parameter setting will not succeed. IPower does not support
modification of parameters marked with
Rules for battery protection voltage:
A. Over voltage limiting voltage(16.2/32.2/64.4V) ≥ Over voltage
disconnect voltage ≥ Over voltage reconnect voltage +1V.
B. Over voltage reconnect voltage ≥ Low voltage reconnect voltage.
C. Low voltage reconnect voltage ≥ Low voltage disconnect voltage +1V.
D. Low
voltage
voltage(10.5/21/42V).
. Please refer to the following rules for the modification;
disconnect
, the inverter will restart
.
voltage
Low
11
voltage
limiting