Wiring Diagram to Connect to Milltronics BW500
Milltronics BW500
Port 2 setup parameters:
Parameter
P770 (2)* = 3
P771 (2) = 1
P772 (2) = 9.6
P773 (2) = 0
P774 (2) = 8
P775 (2) = 1
P778 (2) = 0
*(2) refers to the primary index (secondary index 0).
Temination
It is important to use a terminating resistor at the extreme ends of your RS-485 network.
A terminating resistor needs to be connected across the A and B conductors of the last
device at each end of the network.
If you are using Belden 9842 cable, the value for termination is 120R, 0.5 W resistor.
7ML19985MA01
SITRANS RD500 – OPERATING INSTRUCTIONS
customer device
RD500
Description
Modbus RTU slave
address 1 to 247
baud rate selectable
no parity
8 data bits
1 stop bit
modem not attached
Bus termination resistors to be 120R.
Recommended cable is Belden 9842.