Siemens SITRANS RD500 Operating Instructions Manual - Page 43

Browse online or download pdf Operating Instructions Manual for Switch Siemens SITRANS RD500. Siemens SITRANS RD500 48 pages. Configuring sitrans rd500 for connection to multiranger with modbus rtu
Also for Siemens SITRANS RD500: Operating Instructions Manual (8 pages), Operating Instructions Manual (8 pages), Operating Instructions Manual (8 pages), Application Manual (6 pages), Manual (11 pages), Application Examples (9 pages)

Siemens SITRANS RD500 Operating Instructions Manual

Wiring Diagram to Connect to Milltronics BW500

Milltronics BW500
Port 2 setup parameters:
Parameter
P770 (2)* = 3
P771 (2) = 1
P772 (2) = 9.6
P773 (2) = 0
P774 (2) = 8
P775 (2) = 1
P778 (2) = 0
*(2) refers to the primary index (secondary index 0).
Temination
It is important to use a terminating resistor at the extreme ends of your RS-485 network.
A terminating resistor needs to be connected across the A and B conductors of the last
device at each end of the network.
If you are using Belden 9842 cable, the value for termination is 120R, 0.5 W resistor.
7ML19985MA01
SITRANS RD500 – OPERATING INSTRUCTIONS
customer device
RD500
Description
Modbus RTU slave
address 1 to 247
baud rate selectable
no parity
8 data bits
1 stop bit
modem not attached
Bus termination resistors to be 120R.
Recommended cable is Belden 9842.
Page 41