- ページ 7

ネットワーク・ルーター Argo-Hytos LubMon ConnectのPDF クイック・スタート・マニュアルをオンラインで閲覧またはダウンロードできます。Argo-Hytos LubMon Connect 7 ページ。

4. Electrical connection

The electrical installation may only be performed by qualified professionals
(trained electricians) with the power off and in accordance with the applicable
standards and guidelines. The manufacturer will accept no responsibility in the
event of improper installation.
4.1. General, plus safety notices
Comply with national and international guidelines for setting up electrical equipment.
Power supply in accordance with EN50178, SELV, PELV, VDE0100-410/A1.
De-energise the system for the installation and connect the device as follows:
(view of connector from the outside)
Fig. 4.1: Pin assignments for the CAN interface
The permissible operating voltage is between 12V and 28 VDC. The sensor cable must be
shielded. Pin 8 und Pin 9 are for the power supply of LubMon Connect and not for the power
supply of the connected bus devices.
 Pin 1 ---
 Pin 2 CAN-L
 Pin 3 GND
 Pin 4 ---
 Pin 5 SHIELD
 Pin 6 ---
 Pin 7 CAN-H
-------- Galvanically isolated --------
 Pin 8 supply + (24VDC)
 Pin 9 supply –
7