Schedule Enable Range: Y or N
When enabled, the local thermostats scheduler function is enabled.
Recovery enable
For Heat Pump Systems. Intelligent setback recovery is an automatic advance start of
heating to allow the system to be at setpoint by the schedule time, without the use of Aux
heating.
Delta Settings : The Delta T Setting is the delta, or difference between, the setpoint and
current temp for determining when a heat or cool call comes on.
The "delta" is the number of degrees away from setpoint.
H/C Delta
Sets the minimum separation between heating and cooling setpoints.
Attempts to lower the cooling below the heating setpoint by this amount will PUSH the
heating setpoint down to maintain this separation.
Same for setting the heating setpoint above the cooling setpoint, it will PUSH the cooling
setpoint up to maintain this separation.
Fan Purge
Heating Delta Stage 1 ON
Sets the delta from setpoint that stage 1 heating starts.
Heating Delta Stage 1 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 1 heating stops.
Stage 1 turns off at setpoint + Delta Stage 1.
Heating Delta Stage 2 ON
Sets the delta from setpoint that stage 2 heating starts.
Heating Delta Stage 2 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 2 heating stops.
Stage 2 turns off at setpoint + Delta Stage 2.
Heating Delta Stage 3 ON
Sets the delta from setpoint that stage 3 heating starts.
Heating Delta Stage 3 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 3 heating stops.
Stage 3 turns off at setpoint + Delta Stage 3.
Cooling Delta Stage 1 ON
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Delta Stage 1 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 1 Cooling stops.
Stage 1 turns off at setpoint - Delta Stage 1
Cooling Delta Stage 2 ON
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Delta Stage 2 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 2 Cooling stops.
Stage 2 turns off at setpoint -Delta Stage 2.
DCN: 2012-11-222-1
Range: Y or N
Range: 3 - 15 degrees.
Range: 0, 30-120 seconds
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Default: Y
Default: N
Default: 3F (1C)
Default: 0 (off)
Default: 1
Default: 0
Default: 2
Default: 0
Default: 3
Default: 0
Default: 1
Default: 0
Default: 2
Default: 0
Page 5