- ページ 6

水ポンプ Armstrong 4039 SeriesのPDF 据付・取扱説明書をオンラインで閲覧またはダウンロードできます。Armstrong 4039 Series 8 ページ。 Belt driven pumps

CAUTION:
Under no circumstances should the pump be used for flushing out the system. In line with CIBSE
commissioning code W: 1994, the pump should be out of line or bypassed during flushing.
NOTE:
Particular care must be taken to check the following before the pump is put into operation:
a)
Pump primed?
b)
Rotation OK?
c)
Lubrication OK?
d)
Pipework properly supported?
e)
Voltage supply OK?
f)
Overload protection OK?
g)
Is the system clean?
h)
Is the area around the pump clean?

WARRANTY

Does not cover any damages to the equipment resulting from failure to observe the above precautions. Refer to
Armstrong General Terms and Warranty sheet. Contact your local Armstrong representative for full information.
Page 6 of 8