AM Series Thermal Insulation Replacement Instruction
1.
Referring to Figure 5, unscrew the four nuts labeled "B."
2.
Remove the entire fan and burner assembly, labeled "C."
Figure 5: Removing the Fan and Burner Assembly
5. Replacing Heat Exchanger's Thermal Insulation
Thermal insulations must be checked every year for any damage, including cracks, chips, or
other damage. If any damage is found they must be replaced.
These instructions will be repeated on each burner in the unit.
Replacing
1.
Unscrew nut from the thermal insulation (see Figure 6).
2.
Use a screwdriver to remove the thermal insulation.
3.
Prepare the screw and the washer to fix the new thermal insulation (see Figure 7).
Figure 6: Screw & Thermal Insulation
07/28/2014
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Kit # 62632006
Removing the Burner – Continued
the Heat Exchanger's Thermal Insulation
Figure 7: Screw & Washer
TID-0120_0A