Step 2) The controller will only notify you when there is a failure
mode whereby the solenoid module (and connected solenoid valve)
will be activated. On the BWS5 system, the solenoid module will be
activated (shutting off the flow of water) upon LAMP FAILURE (see
Fig. 5). To remedy this, replace the UV lamp and restart the system as
per the directions outlined in the Owner's Manual.
Step 3) On the BWS6 system where a UV sensor is installed, the solenoid
module will be activated (shutting off the flow of water) upon a LOW
UV condition (less than 50%) (see Fig. 6). To remedy this, you will need
to address the reason for this low UV condition which may be due to a
dirty UV sensor and quartz sleeve, a lamp that is not emitting enough
UV energy, or a change in the water quality. Please refer to the UV
systems Owner's Manual for corrective action procedures.
Step 4) To determine what position the solenoid valve is currently in, the solenoid module
incorporates three lights on the circuit board (see Fig. 7). When the solenoid is in the OPEN
position a green light will appear on the circuit board beside the word "OPEN". When the valve
is CLOSED, a red light will appear on the circuit board beside the word "CLOSED". And when the
solenoid is in an OVERRIDE position, an amber light will appear on the circuit board beside the
word "OVERRIDE ON".
Figure 7
Solenoid Status
(Colour)
Boil Water Advisory: If any failure occurs on a BLAKE UV system, the water
must not be used for human consumption until the system is returned to a safe operational
mode. If the water is used for human consumption during this period, the water must be
boiled (minimum 20 minutes at a full boil) prior to consumption.
EMERGENCY BYPASS
In a case where the solenoid valve has been activated (valve is closed and no water is allowed
to flow), the solenoid module has the ability to bypass the solenoid valve in case of an
emergency need of water. To initiate this bypass, depress the button labeled "OVERRIDE"
located in the lower left portion of the circuit board (see Fig. 8)
6 |
P a g e
Figure 6
LOW UV
Screens
Figure 5
LAMP FAILURE Screen