Figure 8
Solenoid Bypass
Button
Once this button has been pressed, the system will remain in this
override mode regardless of whether or not the condition causing the
solenoid activation has been remedied or not. To reset the system,
the power to the controller must be shut off and restarted. While
in this override mode the controller will intermittently display a red
"SOLENOID OVERRIDE" screen (see Fig. 9).
Figure 9
SOLENOID OVERRIDE
Screen
DISABLING EMERGENCY BYPASS
In certain regulated applications, the availability , and use,
of the emergency bypass feature may be in violation of the
local, state/provincial codes. If this is the case, the bypass
feature can easily be disabled by physically removing the
bypass button. To accomplish this, carefully use a pair of
needle nose pliers and physically remove the actual bypass
button (marked "OVERRIDE") from the circuit board .
OTHER FAILURE MODES
In the event there is an issue with the solenoid connection from
the IEP cable to the controller, the system will register a "SOLENOID
FAILURE" screen on the controller (see Fig. 10).
Figure 10
SOLENOID FAILURE
CAUTION:
BEFORE PERFORMING ANY
Screen
WORK ON THE SOLENOID MODULE, THE
POWER CORD MUST BE DISCONNECTED
FROM ITS POWER SOURCE (WALL PLUG).
7 |
P a g e