Description
Data type #
40580
OUTSET2
UINT16
40581
OUTRANGE2
REAL
40585
TRIM2
REAL
40589
ERRVAL2
REAL
40591
GRAD_TIME
REAL
40593
NUMTAB
UINT8
40594
TAB1_YA
REAL
40596
TAB1_X
REAL[20]
40636
TAB1_Y
REAL[20]
40676
TAB1_YE
REAL
40678
TAB2_YA
REAL
40680
TAB2_X
REAL[20]
40720
TAB2_Y
REAL[20]
40760
TAB2_YE
REAL
1
Max. +/-22 mA or +/-11 V
2
Automatic correction of parameters in the device.
Each parameter must range within permitted limits. These partly depend on other parameters.
If parameters determining the limits of dependent parameters are changed,
(e.g. measuring range is dependent on the type of measurement), the respective parameters are automatically limited to the permitted parameters. The status will show that such a
correction has taken place.
Limitations of confi guration parameters
Options to combine types of measurement
Register: 40523, 40534
The numerous types of measurement can be combined with
each other in different ways.
See Table 3 page 19
The "earthed" combination is used if both sensors are
connected to each other.
Measuring ranges
Register: 40524, 40535
see table 1 / page 4
16
Default
Description
05h,
Output settings Output 2 (same as Output 1)
at VB604s
01h
Output range Output 2
0
4.0
Minimum value
1
20.0
Maximum value
Output trimming Output 2
0
0.0
Offset trimming
[in % of the output range, setting range +/– 10%]
1
100.0
Gain trimming
[in % of the output range, setting range 90...110%]
0.0
Output value Output 2 in case of a fault
[in % of the output range, setting range -10...+110%)
1.0
Time span between two measured values for gradient calculation of limit values in seconds
Range: 4 x TSET ... 26210 s
Automatic parameter correction
Number of table values
0
0
Number of table values Table 1
Automatic parameter correction
1
0
Number of table values Table 2
Automatic parameter correction
-10.0
Table 1: Y-value (-10%) in % of the measuring range
0.0
Table 1: X-values in % of the measuring range
0.0
Table 1: Y-values in % of the measuring range
110.0
Table 1: Y-value (110%) in % of the measuring range
-10.0
Tabelle 1: Y-Wert (-10%) in % vom Messbereich
0.0
Tabelle 1: X-Werte in % vom Messbereich
0.0
Tabelle 1: Y-Werte in % vom Messbereich
110.0
Tabelle 1: Y-Wert (110%) in % vom Messbereich
Operating instructions V604s Be
–20...20 [mA] / –10...10 [V]
–20...20 [mA] / –10...10 [V]
1
1
1
2
2
2
Due to linking and scaling, the measuring ranges are rescaled
to different ranges.
This is automatically realised in the device.
Abbreviations:
k
:
SCALE1
1
k
:
SCALE2
2
T
...T
INPRANGE1
1a
1e
T
...T
INPRANGE2
2a
2e
Matrix
Input 1
Input 2
Input 1 + 2
Input 1 - 2
Input 2 - 1
Min1 = T
* k
Max1 = T
1a
1
Min2 = T
* k
Max2 = T
2a
2
Minimum value
Maximum value
MEAS1
MEAS1
Min1
Max1
Min2
Max2
Min1 + Min2
Max1 + Max2
Min1 – Max2
Max1 – Min2
Min2 – Max1
Max2 – Min1
Camille Bauer
* k
1e
1
* k
2e
2