ボイラー AKKAYA-BLOWTHERM SBK-YSB-HYBのPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。AKKAYA-BLOWTHERM SBK-YSB-HYB 20 ページ。 Steam boilers
briquette without letting any air leakage.Side section and backside of the boiler
are being built with brick and briquette as seen the figure to make ash space.
The place where the furnace and reverse chamber is attached (fig 1) ,must be built
by fire bricks.It is height must be as much as explotion doors height.
If the boiler will be used with solid fuel or gas fuel ,concrete step must be
spilled as we make scotch type boiler to the place where the boiler wÕll land and
the boiler must be setted on this concrete step.A hole which the barrel of burner
can enter in ,is drilling on the door of coal inlet.Appropriate parts of assemblying
are done on the connecting flange of the burner.
CONNECTION OF SCOTCH TYPE OF STEAM BOILER
Fig 4 :
Connection of scotch type steam boiler
Fitting up steam boiler and chimney connecting must be done by qualified service.
Attaching safety and control Õnstruments connectings existed Õnstallition.
Similiar services are made by recommended company by qualified service.
The height of the boiler 2m higher than the boiler height.
1 m distance must be between boilers and at least 1 m distance from side wall
of the boiler There must be at least two doors facing each other .one of them
must have ventilation to let to the boiler room.
These doors must be 2 m height and 0.6 m width.These doors must be divided
from other places.The boiler room must be ventilated.Pressure decrase can be max.
0.5 mbar in the boiler room.
9
Concrete step must be done in appropriate dimensions to the place where landing
boiler and the boiler must be placed there.
A hole which the barrel of the burner can enter in ,is drilling on the door of coal
Appropriate parts of assemblying are done on the connecting flange of the burner.
boiler and the boiler must be placed there.
Burner must be fitted up by these parts.
CHøMNEY CONNECTION
Boiler must be connected chimney by connecting parts which have the same
dimensions of stack connection of the boiler.
The distance between chimney and the boiler must be less than 3m.If it is possible
If you have to use elbow ,you cant use more than two elbows .
Becareful about sharp turning because tar can be formed Õn the chimney by
by chimney fumes pipe.Too long chimney connection pipes in horizantal section
cause poor draft of chimney because of quick cooling .Chimney draft is very
is important for the burning quality .The diameter of chimney must be in appropriate
dimensions for your boiler.
ASSEMBLøNG ACCESSORIES OF STEAM BOøLER
All accessories must have the specifications and quantities as inidicated in norms and standards
The faÕilures caused by the accessories provided by the customer is not at our responsibility and
guarantee conditions do not apply.
Fig. 5 :
Accessories Of Steam Boiler
10