AMC AMC-1225 사용 설명서 - 페이지 15

{카테고리_이름} AMC AMC-1225에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AMC AMC-1225 17 페이지. Sensor modules

AMC-1225 SENSOR MODULES
NOTE:
If the sensor has been replaced, adjust the SIGNAL first, then proceed with LOW alarm
and HIGH alarm adjustments. Signal calibration is performed using a digital multimeter
set to measure DC voltages to two (2) decimal places (e.g. 0.00 Volts).
The SIGNAL adjust is used to set the sensitivity of the sensor. This is done by exposing the
sensor to the LOW alarm concentration of gas. The voltage associated with signal can be
measured between the negative (-) power line on the output terminal block and the test point
Figure 5-1Figure 5-1
next to the signal trimmer, see
. The voltage measured at the signal test
point should be approximately 1.20 Volts.
When calibration is completed, remove the calibration chamber, replace the sensor element
while observing the correct polarity, and then reinstall the cover plate with the four screws.
CAUTION:
Only qualified personnel should perform the actual calibration. Users are advised to
consult The Armstrong Monitoring Corporation as to the recommended calibration gas
concentration for the application, and any other questions.
14