Fig. 6.3 Alarm limits adjustment
To set LL to 0% and HL to 100%, set the first and the last segments to "fast flashing red"
using the buttons
and
, then press
to save and quit (Fig. 6.4 a, b).
If you need only one limit (lower or upper), press and hold the button
for 3 seconds, set
the first or the last segment to "slow flashing green" using the button
or
, and press
to save and quit (Fig. 6.4 b, c).
Fig. 6.4 Setting the alarm at the limit values
7. Operation
When the input signal is connected and the supply voltage is turned on, the display shows
the process value as shown in Fig. 7.1.