2.4.6 Multiple AX-CZM Module Power and Reset Wiring

24
VDC
Host Panel Reset Input
(momentary short/contact closure)
Host Panel Reset Input
(momentary short/contact closure)
Figure 13 – Multiple AX-CZM Module Power and Reset Wiring
Note: Loss of 24 VDC will transfer the failsafe (inverted) trouble relay contact. The HOST FACP normally
open (momentary closed for reset) input is unsupervised, wiring must be within 20 feet of the reset contact
in conduit.