Advanced Axis AX-I/O-48 설치 지침 매뉴얼 - 페이지 9

{카테고리_이름} Advanced Axis AX-I/O-48에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Advanced Axis AX-I/O-48 20 페이지. Switch led modules

Advanced Axis AX-I/O-48 설치 지침 매뉴얼
Note: When utilizing multiple Switch LED Module's, within the same enclosure, 24 VDC power and the P-
BUS (485) communications can be daisy chained from the first Switch LED Module to the next module, then
from that module to the following module, etc.

4.2 485 (AX Series P-BUS) Wiring

Connect the P-BUS (RS485 serial communications) terminals A and B of the Axis
and B input terminals of the Switch LED Module (see figure 8). If this is the last module connected to the AX-CTL
P-BUS (RS485 serial communications), set DIP switch 6 (485 Comms EOL) one the Switch LED Module to the
"ON" position (see figure 6).
Note: When utilizing multiple Switch LED Module's, within the same enclosure, 24 VDC power and the P-
BUS (485) communications can be daisy chained from the first Switch LED Module to the next module, then
from that module to the following module, etc.
4.3 24 VDC & 485 (AX Series P-BUS) Daisy Chain Wiring
When utilizing multiple Switch LED Modules within the same enclosure, the 24 VDC power and P-BUS (485)
communications can be daisy chained from one module to the next module.
Wire 24 VDC and the P-BUS (RS485 communications) to the screw terminal inputs on the first Switch LED Module
(see figure 8). Plug the supplied 10-Way (IDC) ribbon cable into the PL2 (10 pin) serial connection on the Switch
LED Module, connect the other end of the 10-Way (IDC) ribbon cable into the PL3 (10 pin) serial connection on the
next Switch LED Module (see figure 9). This method of distributing both the power and communications can be
continued to other Switch LED Modules, however power requirements must be monitored to confirm there is
enough power to supply all of the connected modules.
www.advancedco.com
www.advancedco.com
Figure 8 – Switch LED Module Wiring
AX
AX-CTL base card to the 485 A
9