6.7. Remote sensor (Optional parts)

• For the installation method, please refer to the INSTALLATION MANUAL of remote
sensor.
Connection methods
• Connection terminals
Controller PCB
• Wiring arrangement
• Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
• Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
• Function Number "30":
Set the Setting Number to "00". (Default)
• Function Number "31":
Set the Setting Number to "02".
* Refer to "7.4. Function setting" for details about Function
Number and Setting Number.
] 1
En-13
Remote sensor
terminal (CN8)
Controller PCB
Clamps
Cable tie
Shield cable
(Field supply)

6.8. IR receiver unit (Optional parts)

• For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
Connection methods
• Connection terminals
Controller PCB
• Wiring arrangement
Controller PCB
] 1
IR receiver unit
terminal (CN18)
Core
Cable tie*
(Field supply)
Clamps