outdoor air intake duct installation
Mount the sensor in an outdoor air intake by drilling a ¼ inch hole within 8
inches of outside. Angle the hole towards the outside. Insert the temperature
sensor into the intake pipe until the sensor is at least 2 inches outside the
structure in the intake pipe. Seal the hole and secure the wire so it cannot
be accidentally pulled out.
Drill Hole in
Pipe & Seal
Connect to
Humidistat
(ODT)
Figure 4: Outdoor Temperature Sensor in Furnace Intake Pipe
10
|
CommerCial humidiStat
INSIDE
OUTSIDE
Furnace
Fresh Air
Intake
OAT (Outdoor
Air Temperature)
Sensor
2" min.
Form 16767