Anderson ANM75 운영 매뉴얼 - 페이지 8

{카테고리_이름} Anderson ANM75에 대한 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Anderson ANM75 18 페이지.

– Fuel type and fuel supply pressure
– Adequate fresh, clean, combustion air
– Humidity, altitude, temperature and presence of damaging corrosive gases of the
supply air.

10.5 Burner Mounting

1. Mounting methods
The installation modes of ANM75 series burners are as follows: process air parallel
to combustion flame, process air vertical to combustion flame, the former can be
divided into blower installed in the air duct and outside the air duct, the specific
diagram shows as fig 6 that the air duct burner installed in the center of the air duct.
2. Corner distance
When laying in the duct, allow least length downstream of the burner should be
1100mm to avoid flame impingement; as fig 7 below shown, please see fig 5 for
flame length.
When burner longer than 900 mm, use a hanger or a pedestal to support the blower
and motor. Process air velocity must be within the limits.
Anderson Thermal Soluions(Suzhou)Co. ,Ltd.
Anderson Thermal Solutions – ANM75 Burner Operation Manual
Fig 6. ANM 75Series Burner Installation Layout
Fig 7. ANM75 Series Burner Installation Layout
6