Commissioning

The product is delivered in standby mode where it sends only the life frames.
To activate the product, press the push button for 2 seconds; the LED should blink 3 times to
indicate the switch to operating mode.
You can also pass a magnet over the diamond (area indicated on the red circle).
It is also possible to activate the product remotely by downlink (see the section Configuration).
NOTE
Approaching the magnet is equivalent to pressing the push button.
Test frame emission
When the product is in its operating mode, it is possible at any time to send a test frame. To do this, you must press
the push button briefly (less than 2 seconds) or pass the magnet briefly.
Periodic frames
This period of readinǵ and transmission is configurable by the user, with a minimum of 10 minutes.
NOTE
By default, this period is set to every hour.
Keep alive frames
The period of the life frames is configurable by the user, with a minimum of 10 minutes.
NOTE
By default, the period for sending life frames is set to once a day.