Servicing Requirements
Troubleshooting Guide
Spare Parts Information
Maintenance & Spare Parts Instructions
1
Ensure mains water is turned off and
remove Outlet Valve from cistern as per
the instructions on page 17.
Servicing is only required in instances where outlet valve operation is found to be faulty.
If the urinal flushes for 20 seconds or more ► 1. Ensure that the flush volume is correctly adjusted for
ON
Dust Cover
If Outlet Valve leaks ► Inspect seal for damage and replace if necessary.
If short flushing ► Check pneumatic tube is pushed into the bridge and button
If any other issues arise ► Consult a plumber or Caroma After Sales Service.
Caroma Invisi II Outlet Valve compatible Spare Part Kits are:
237 173 Containing - 1 x Complete Urinal Outlet Valve
237 070 Containing - 10 x Diaphragm Seal
Refer to - Maintenance & Spare Parts Instructions
2
Seal
Wash seal to remove any dirt and inspect
for damage. If necessary remove seal and
replace (Spare Part Kit 237070).
the installation.
2. Where the urinal flushes for more than 20 seconds,
the inlet valve flow rate must be reduced. This is
achievedby carefully adjusting the Isolating Tap
down.
OFF
3. Flush urinal several times to confirm settings.
NOTE: In some instances, particularly single stall
urinals, it maybe necessary to adjust the Isolation Tap
down very low (almost to the off position).

Servicing - Outlet Valve

3
Re-assemble complete Outlet Valve and
refit into cistern. Turn mains water back on,
wait for cistern to fill and test both buttons
to ensure they activate the outlet valve.