Supplement operating manual for DREHMO i-Matic actuators with integrated

2.3.1 Accesses for master input data ( actuator feedback signals)

The following table gives detailed information about the addresses of the actuator feedback signals.
Register Bit
Coil
0x201
0..7
1..16
8..15
0x202
0
17
1
18
2
19
3
20
4
21
5
22
6
23
7
24
8
25
9
26
10
27
11
28
12
29
13
30
14
31
15
32
0x203
0
33
1
34
2
35
3
36
4
37
5
38
6
39
7
40
8
41
9
42
10
43
11
44
12
45
13
46
14
47
15
48
Wenden, 21.03.12
Prepared by: Ste
MODBUS fieldbus interface
Signal
Position value Low-Byte
Position value High-Byte
General fault signal 1
General fault signal 2
Phase failure
Failure internal 24 V DC
Failure externally supplied 24 V
DC
Torque in OPEN direction
Torque in CLOSED direction
Drive in fail-safe
Drive moves to OPEN (only
statically)
Drive moves to CLOSED (only
statically)
Drive in end of travel position
OPEN
Drive in end of travel position
CLOSED
Drive in end of travel position
OPEN+Drehmo
Drive in end of travel position
CLOSED+TORQUE
Motor too hot
Drive in the remote mode
Drive in the local mode
Drive locally controlled
Activation of discrete commands
Drive in the learn mode
Locking
Torque limit deactivation in OPEN
Torque limit deactivation in
CLOSED
Start-up bridging in OPEN active
Start-up bridging in CLOSED
active
Local_ind = NOT Remote
Emergency travel active
Approach fail-safe position
Pulse generator active
Intermediate position 1
Intermediate position 2
Drive does not start
Meaning
0...1000ppt actual position value
General fault signal 1 is active
General fault signal 2 is active
One of the three phases has failed
Only possible in case of external supply
Only possible in case of external supply
Max. torque in the OPEN direction
exceeded
Max. torque in the CLOSED direction
exceeded
Drive is in the fail-safe mode
Movement in direction to OPEN position
signal
Movement in direction to CLOSE position
signal
End of travel message only acc. to
position
End of travel message only acc. to
position
End of travel message only if path and
torque
End of travel message only if path and
torque
Signal excess temperature motor
Display of the operating mode
Display of the operating mode
Drive is locally controlled
A remote command OPEN or CLOSE
can be given (Automatic mode = 0)
Display of the operating mode
Parameter setting for remote command
Parameter setting for deactivation
Parameter setting for deactivation
Parameter display
Parameter display
Drive is not in the remote mode
Status indication
Parameter display
Parameter display
Message active between Z and ZS 1
Message active between ZS 2 and
OPEN
Warning message
Page 5 of 18