Fan Control Mode
There are 3 modes for fan speed control. Wall, ducted and constant airflow/ volume
(CV) mode (CV - Pro models only). In wall or ducted mode, the fan speeds are pre-
determined at the factory and does not use the airflow sensor.
In CV mode (Constant Airflow/Volume), the fan will automatically adjust the fan speed
to maintain the desired airflow. After the first 15 minutes of operation the fan enters
calibration mode to determine the most efficient mode of operation.
Calibration Reset
In some circumstances it may be necessary to reset the calibration settings (if the fan
was covered to prevent dust/damage/or poor weather outside).
Reset the calibration by configuring the fan for wall or duct mode (F-0 or F-1), turn the
product off and on and re-configure back to CV mode (F-2).
The fan will calibrate after 15 minutes or by holding the pullcord for 5 seconds.
Pullcord
Switches the fan from trickle to boost (for boost overrun time)
o If the overrun time has been set to 0 (disabled), a default overrun duration
of 5 minutes will take place.
This will override LS comfort mode, boosting the fan immediately
An activation when a Pullcord/LS (Light Switch) boost is already active shall cancel
overrun timer (RH boost sources remain unaffected)
Data Logger Menu
* When the display is rotated the decimal point will no longer display; eg. 055 represents
5.5KWh
Display text
tot run 00y 00d
Tri run 00y 00d
Boo run 00d
rhu run 00d
tot EnErgy 00.0
24h EnErgy 00
Cutting the power to the fan will not erase the stored data. To reset the data, hold
pullcord for 14 seconds while in the data logger menu.
Description
Total run time in years and days
Trickle speed run time in years and days
Boosted run time in days
Humidity boosted run time in days
Total Energy used displayed in KWh*
Energy used in last 24 hours displayed in Wh