Mandatory installation of a safety device in a frost free location (or
any other new device which limits the tank pressure) to 850 kPa
according to the nominal pressure, with a size of 3/4'' on the input
of the water heater, respecting the local regulations .
Operate regularly the discharge of safety device to prevent scaling and
check that it is not blocked.
To drain the device switch off the power and the supply of cold water,
open the hot water faucets and manipulate the safety valve.
The pipes used must support 1 MPa (10 bar) and 100°C.

Cold Water Inlet

Cold water piping should be provided with a 350 – 500 kPa Pressure
Limiting Valve at the point of cold water connection to the
water heater. In addition to the Pressure Limiting Valve, it is a
requirement of AS 3500.4 & NZBC G12 that both a Stop Valve and a
Non Return Valve are installed upstream of the Product.
 
No parts (stop valve, pressure reducer, etc.) must be placed between the
pressure limiting valve and the cold water inlet of the water heater,
apart from a copper pipe.
 
Note: Since limited water discharge from Pressure Limiting Valve is
normal in the heating operation, the discharge pipe needs be
connected to external drain.

Hot Water Outlet

Where a maximum hot water delivery temperature is specified by local,
state or federal regulations, a tempering valve shall be installed at
the hot water outlet, as required.
The included specified Pressure & Temperature Relief valve must
be installed as shown in the schematic. The PTR valve should
be connected to a drain point to accommodate discharge as a
5