3). COMMISSIONING

3.1) Precautions

ESSENTIAL - a safety valve at 3BARS, an automatic air vent and an expansion vessel
a).
make sure that the heating system is primed with water
b).
check the pump for circulation
c).
check the boiler for electrical power
d).
press the ON/OF button
e).
check the two-stage output switching
f).
switch back to the first stage

3.2) Setting control temperatures

Setting the control – stage 1 = 80degC; stage 2 = 75degC
PROCEDURE
SET 1 – stage one
SET 1 – temperature must be greater than SET 2
Minimum temperature is 20degC
Maximum temperature is 90degC
Possible resetting of SET 1 is 3degC below and allow 3 minutes to reset
Leave the settings as provided at the Factory
3.3). Altering the settings
A). Touch SET 1, hold for 5 seconds – light 6 illuminates
B). Make up & down adjustments on 3 or 4
C). Touch SET 1 to fix the setting
Main screen flashes acceptance and light 6 goes out
After about 10seconds, the actual measured temperature is given
D).
Touch SET 2, hold for 5 seconds – light 6 illuminates
E).
Make up & down adjustments on 3 or 4
F). Touch SET 2 to fix the setting
Main screen flashes acceptance and light 6 goes out
After about 10seconds, the actual measured temperature is given
ALARM SIGNALS
Alarm light 7 ignites and the main screen signals :-
< 000 > faulty thermostat sensor
< HA > high temperature lockout
< LA > low temperature recorded
SET 2 – stage two
1 - 7 weekdays setting
2 - touch change control band
3 - touch control setting positive
4 - touch control setting negative
5 - indication of touch control –
light means action
6 - light means controls in action
7 - light means alarm
7