1.
Sentry™ Safety Sensor: Pilot lamps provide constant visual monitoring of normal operation. In the event of
power or lamp failure the safety sensor indicates an alarm condition. The safety sensor is capable of operating an
optional audio alarm and/or solenoid valve.
2.
Audio Alarm: Activated by the Safety Sensor, alerts the user to any malfunction detected.
3.
Time Delay Mechanism: Provides a 2-minute warm up period during which the ultraviolet lamp achieves its full
germicidal output before the water is allowed to flow through the water purifier. The time delay mechanism is used
in conjunction with, and is electrically connected to the Solenoid Valve.
4.
Solenoid Valve: Operated in conjunction with the Safety Sensor or Time Delay Mechanism, this valve prevents
water flow through the water purifier when an abnormal condition is detected or in the event of power failure.
5.
SureFLO™: Flow Control Valve, limits water flow to the rated capacity of the purifier. The flow control valve is
located in line prior to the water purifier, and should be protected from ultraviolet exposure by the use of a 90-
degree elbow fitting between the flow control valve and the water purifier.
6.
Elapsed Time Indicator: A non-resettable display of the water purifier operating hours. Useful for scheduling and
recording maintenance and lamp replacement.

MAINTENANCE

The water purifier is designed to operate with a minimal amount of maintenance, providing the water quality does not
exceed maximum concentration levels, see "WATER QUALITY" in the "PRODUCT APPLICATION" section.
Ordinary maintenance consists of;
• Lamp replacement is recommended every 10,000 hours of operation, approximately 12 months of continuous service.
• Cleaning of the quartz sleeve, when conditions warrant.
• Always disconnect the water supply and completely drain the water purifier if it will be subjected to
temperatures below freezing, for extended periods of time.
I

NSPECTION

1.
Regularly inspect the water purifier to ensure that the germicidal lamp is still in operation.
• An LED indicator light, located on the ballast, provides visual indication of germicidal lamp operation.
This provides an indication of lamp operation and does not indicate the level of ultraviolet intensity or
transmission through the water.
• On purifiers so equipped, the Sentry™ Safety Sensor provides visual indication of ballast and ultraviolet
lamp operation.
2.
To ensure proper operation of the water purifier, regular biological testing should be performed on a schedule
recommended by local public health authorities, or at minimum; at installation, quarterly for the first year of
service and annually, at lamp replacement, for the life of the water purifier.
7