AuCom CSX-022 사용자 설명서 - 페이지 5

{카테고리_이름} AuCom CSX-022에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AuCom CSX-022 13 페이지.
AuCom CSX-022에 대해서도 마찬가지입니다: 사용자 설명서 (12 페이지)

Section 4
Initial Start Voltage
Initial Start Time
Soft Stop Time
710-02407-00G
Adjustments
Select the Initial Start Voltage (A).
Application
Centrifugal Pump
Submersible Pump
Screw Compressor
Conveyor
Crusher
Fan
Other applications
Select the Initial Start Time (B).
The start ramp defines how long the soft starter will take to
increase voltage from the initial start voltage to full voltage.
The Initial Start Time does not control the time the motor will
take to reach full speed.
1. Set the Initial Start Time to 20 seconds.
2. Set the Initial Start Voltage as required for the application.
3. Attach a current monitoring device to output T1.
4. Start the motor under normal load conditions. Record the
time required for the measured current to fall to (or
below) the motor's rated full load current (t
the motor.
5. Set Initial Start Time = t
NOTE
The Initial Start Time must be long enough for the motor to
reach full speed before the soft starter enters bypass mode.
Select the soft stop ramp time (C).
Soft stop extends the time soft starter takes to reduce voltage
to zero.
The ramp time does not control the time the motor will take to
stop completely.
Initial Start Voltage
Start Ramp Time
Stop Ramp Time
Suggested Initial
Start Voltage
50%
60%
70%
) then stop
1
.
1
CSX
ADJUSTMENTS
Page 5