Daylight (daylight saving time changeover)
Setting range
ON / OFF
Choose whether you want the change to summer / winter time to be automatic or manual.
ON:
The controller's built-in clock automatically changes + / - one hour on
the standardized days for daylight saving time changeover for Central
Europe.
OFF:
You change manually between summer and winter time by setting the
clock backward or forward.
ECL address (master / slave address)
Setting range
0 ... 15
This settting is relevant if more controllers are working in the same ECL Comfort system (connected via
the ECL BUS) and / or ECA units are connected.
0:
The controller works as slave. The slave receives information about the
outdoor temperature (S1), system time, and signal for DHW demand from
the master.
1 ... 9: The controller works as slave. The slave receives information about the
outdoor temperature (S1), system time, and signal for DHW demand
from the master. The slave sends information about the desired flow
temperature to the master.
10 ... 14:
Not used.
15:
The controller is master.
The ECL Comfort controllers can be connected via the ECL BUS to perform a larger
system.
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have to receive information
about outdoor temperature and system time.
20
VI.KT.F2.02
7198
Factory setting
ON
7199
Factory setting
© Danfoss 06/2008
DH-SMT/DK
Type
Use this setting to change your application or restore your factory settings.
116:
Constant temperature control of DHW circuit.
130:
Weather compensated control of heating and boiler systems.
5 sec.
Start the chosen application.
Factory settings are restored. All personal settings will be deleted. It is recommended to
15
make a note of your personal settings in the 'Settings overview' for future use.
DH-SMT/DK
Setting range
116 / 130
VI.KT.F2.02
© Danfoss 06/2008
7600
Factory setting
116
21