Danfoss REP24CO1 사용자 지침 - 페이지 4

{카테고리_이름} Danfoss REP24CO1에 대한 사용자 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss REP24CO1 12 페이지. Electronic proportional heat / cool thermostat

Danfoss REP24CO1 사용자 지침

Product overview

GB
This thermostat is designed for fan coil and chilled beam
applications alongside proportional valves and actuator systems
where a 0-10v proportional control output is required.
The thermostat also has a single speed fan output.
The operational mode of the fan (auto or continuous) is selected
at time of installation via DIL switches accessible on the rear of
the unit.
When the unit is in standby the fans are switched off .

Installation

First remove the wallplate from the back of the unit.
Fix at a height of approximately 1.5m from the fl oor, away
from draughts or heat sources such as fan-coil outlets,
sunlight or offi ce equipment.
Wiring
4