Step 6
Room temperature sensor
Use the new enclosed
temperature sensor and
connect to CC3000.
Place it on the same location as
the present sensor.
Note: For DFC 350/450 the
temperature sensor must be
placed 160 cm above ground
level.
Connect the room temperature
sensor to green connector J11
Pin No: 1 and 2
System setup
10
CC3000 controller
At startup insert SD card in the slot located on the side of the CC3000 controller.
This will allow you to select the config file for your free cooling system..
Note: until the SD card is inserted the controller will remain inactive and the buttons will not
function.
For advanced use of the CC3000 controller please refer to the user manual for this product.
Keep sensor clear
of surfaces