Contemporary Controls AI-SRVR-1485D 매뉴얼 - 페이지 14

{카테고리_이름} Contemporary Controls AI-SRVR-1485D에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Contemporary Controls AI-SRVR-1485D 20 페이지. Arcnet server to ethernet client

Contemporary Controls AI-SRVR-1485D 매뉴얼
All fields in the center and right columns of Figure 7 require numerical values:
IP Addr
Netmask
Gateway
DNS #1
DNS #2
Nodelist Timeout
FIFO Depth
TCP Port
UDP Port
EDITING IN FIELDS REQUIRING ENTERED VALUES:
in the Function field. Use the Tab key to advance from field to field. Within each field,
use the cursor arrow keys to position the cursor and the backspace key to erase
characters to the left of the cursor.
CTRL-V toggles the editing mode between the default OVERTYPE: OFF (characters are
inserted as you type) and OVERTYPE: ON (characters are replaced as you type).
EXPLANATION OF EACH FIELD
For the NETWORK configuration at the top of the screen, first set the Function to either
SERVER (if Ethernet clients are to access your ARCNET) or to PROXY (if you plan to
set up an Ethernet backbone between nodes in separate ARCNET LANs).
The Boot Protocol is the next item to be configured. If the IP address is to be set via
Dynamic Host Configuration Protocol, the DHCP option should be selected. When
DHCP is in effect, the following 5 fields are ignored:
DNS #1 and DNS #2. If a fixed IP address is to be used, then NONE should be
selected and the five fields listed in the previous sentence should be changed to values
that are appropriate for your Ethernet network.
* NOTE: If AI-SRVR units connect to the network through routers, this is the address of
the router through which access is gained to the rest of the network or to the Internet.
Next, the BRIDGE fields should be configured.
The Node ID can be any value from 1 through 255 so long as the designated value is
unique within the ARCNET network to which it belongs.
Speed can be set to 156kbs, 312kbs, 625kbs, 1.25Mbs, 2.5Mbs, 7.5Mbs or 10Mbs.
The 7.5Mbs option is not recommended, but it is provided if a special need exists.
* NOTE: The TB5 and CXB transceivers only support 2.5 Mbps. The 485X transceiver
only supports 1.25 Mbps, 2.5 Mbps and 5 Mbps.
is 192.168.92.68 by default.
placing the unit into service is highly recommended.
is the subnet mask — 255.255.255.0 by default.
is 192.168.92.1 by default. If your Ethernet LAN does not have a
gateway, set this value to 0.0.0.0.
is the IP address of the chosen Domain Name Server (if one is
desired at all). It is 0.0.0.0 by default.
is 0.0.0.0 by default.
is 1 by default, but can be set from 1–100000.
is 5 by default, but can be set from 1–10.
is 5001 by default.
is 5001 by default.
TD000200-0MB
14
Defining a new address before
The default cursor position is
IP Addr, Netmask, Gateway*,