Data Aire dap4 touch 빠른 시작 매뉴얼 - 페이지 2

{카테고리_이름} Data Aire dap4 touch에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Data Aire dap4 touch 9 페이지. Modbus tcp/ip protocol integration
Data Aire dap4 touch에 대해서도 마찬가지입니다: 사용자 설명서 (8 페이지), 설치 지침 (2 페이지), 프로토콜 매뉴얼 (13 페이지)

Data Aire dap4 touch 빠른 시작 매뉴얼
Alarm
Menu
Esc
Up Arrow
Enter Arrow
Down Arrow
The main screen allows you to see the current unit status (temperature, relative humidity and operating mode – cool-
ing, humidification, etc.).
Before powering unit ON, check that power is available and proper connections have been completed.
Note: The unit is shipped with the control power in the OFF (Off by Key) position.
Turn the disconnect switch to the ON position. The controller display keys and screen will illuminate and the proces-
sor will conduct a self-test (the screen will remain illuminated with no messages until the testing is complete). The
self-test takes approximately 20 seconds. Once completed, the main menu screen will be displayed.
The main menu screen will display the unit type, date and time, and unit status. In addition, the screen will scroll and
display the temperature, relative humidity and operating mode.
The unit status will indicate the unit:"OFF by Key."
The unit may be turned ON at any time. Hold the ESC key for approximately 5 seconds. The display will continue to
scroll and display messages. At the same time the unit status is changed to "Unit On". Once powered there will be a
5-600 second start delay indicated by "Time Before Start: XXs".
Note: The start time delay is programmable from 5-600 seconds (Menu J – Factory Settings). The factory setting is 5
seconds.
For initial programming of setpoints, alarms, delays, etc. it is not necessary to have the unit ON. With the unit in the
"OFF by Key" mode, all settings are available to view and change (other than Menus J – Factory Settings and L –
Configure Inputs/Outputs) if the proper password is entered.
Once the desired settings are complete, change to the Unit to ON by holding the Esc Key for approximately (five) 5
seconds.
To access any Menu a numerical password is required.
To enter the Menu and Sub-Menu screens, press the MENU key on the display panel. A password will be requested.
The password is a four digit entry (including 0). Units are shipped from the factory with the password requirement
bypassed to accommodate start-up and set-up.

Button Functions

Allows viewing of active alarms
Silences audible alarms
Resets active alarms
Allows entry to Main Menu
Return to previous screen
Hold to turn ON or OFF
Allows scrolling to next screen
Allows values changes (increase)
Allows entry to menus
Advances cursor
Returns to previous screen
Allows value changes (decrease)

Powering the Unit ON/OFF

Accessing Menus/Passwords