Enter Menu A by pressing the MENU key. Use the UP or DOWN key to scroll through the menus. Press the UP or
DOWN key until "A. On/Off" (factory setting) appears and is highlighted. Press the ENTER key.
The following will appear on the display screen:
The curser will be flashing at the upper left hand corner. Press the ENTER key. The curser will move to the "Change
to: SWITCH OFF". Press either the UP or DOWN button to change the status. Press the ENTER key to save the
setting.
l If selecting SWITCH OFF the STATUS will change to: OFFbyKey. The unit will be OFF
l If selecting SWITCH ON the STATUS will change to: UnitOn. The unit will be ON
l When switching from the SWITCH OFF selection to the SWITCH ON (and pressing the ENTER key), the
following message will appear: Time Before Start: XXs
Note: The start time delay is programmable from 5-600 seconds (Menu J – Factory Settings)
Once a selection is made, to leave MENU A, press the MENU key. The Main Menu screen will continue to display
other menus (B, C, E and F). To look at any of these menus scroll to the desired menu. Press the ENTER key. If you
choose to return to the Main Screen, press the Esc key.
MENU B allows viewing and changing of Setpoints (Service Level password is required for entry)
Press the UP or DOWN key until "B. Setpoint" appears and is highlighted. Press the ENTER key.
Use the UP or DOWN key to scroll through the screens. Menu B has two screens.
The following will appear on the first Menu B screen (values are for reference only):
Press the UP or DOWN key. The following will appear on the screen:
On/Off Unit
Start-up Delay:
Start-up Mode:
Status:
Hold ESC for 5 seconds to turn unit ON or OFF

MENU B - SETPOINTS

Setpoints
TEMP SETPOINT:
TEMP DEADBAND:
STAGE to STAGE:
ENGY SVR SETPT:
DEADBAND:
CHANGE OVER:
Setpoints
HUM SETPOINT:
HUM DEADBAND:
5s
Off
Unit On
72.0°F
2.0°F
0.3°F
50.0°F
1.0°F
2.0°F
50%
3%