Thank you for choosing 4EVAC as your Voice Evacuation System solution.
4EVAC Impact is a 19" rack format, EN54-16 certified Voice Evacuation System, dedicated to medium to
large installations. The Impact system is capable of both standalone and network operation, for a wide
selection of peripheral devices and remote extensions. 4EVAC Impact is certified in accordance with EN54-
16 and EN54-4, which are harmonized standards under the Construction Products Regulation, mandatory
in the European Union.
The 4EVAC Impact system is fully compatible with the Compact 500 Voice Evacuation System. This means
that both systems can be connected to one network, running the same protocol in peer-to-peer
architecture, operating within the same space of voice evacuation zones, sharing the same audio messages,
BGM broadcasts, microphone consoles, I/O extensions and cabling infrastructure.

1. General information

4EVAC Controller is the head unit of the 19" rack mounted Impact Voice Evacuation System. The Controller
covers complete EN54-16 certified functionality, as well as a variety of features essential to Public Address
applications.
4EVAC Controller incorporates 16 monitored contact inputs; 8 GPO, 4 relay outputs, 2 analogue audio
inputs and 2 outputs. In addition, local network interfaces for max. 16 local peripheral devices (e.g. mic
consoles) and 2 global network ports for interconnecting multiple systems in a redundant ring topology
are included.
The Controller is designed to work with 4EVAC DCA2.500 power amplifiers over a 4EVAC proprietary AMP
LINK protocol. The Controller can also be easily integrated with any third-party PA/VA power amplifier.

2. Front indicators

POWER

Indicates if the Controller is being powered and if the system is properly booted.
OFF
GREEN continuous
GREEN blinking
Author:
Not powered
This device is powered and operational.
This device is booting after power up / reset.
Page 3 of 14