Daisy-Chain Installation —
Gigabit SPAN Switch hardware installation is illustrate in Figure 5.
Figure 5 - Daisy-Chain Installation
To connect another 4X16SP-1000BT into a Daisy-Chain configuration, refer to FIGURE 5
and follow these steps:
Step 1. Two 100-240 VAC, 50-60 Hz power source inlet connections are provided
for each 4X16SP-1000BT Copper Gigabit SPAN Switch. Use of the second
power source is strongly recommended to assure uninterrupted monitoring.
Connect both AC power cables into the IEC 320 inlet connectors, respec-
tively, of each 4X16SP-1000BT Copper Gigabit SPAN Switch. Plug the
power cables into the external power source, furthermore, connecting the
second power cable to a different external power source circuit than the first
power cable eliminates power as a single point of failure. The front panel
POWER 1 and 2 LEDs illuminate indicating power 1 and 2, respectively,
are on. Either LED not illuminated indicates a defective power source and
immediate investigation is required to insure redundant power integrity.
4X16SP-1000BT Copper Gigabit SPAN Switch • USERguide
A simplified Daisy-Chain 4X16SP-1000BT Copper
15