LOOP
Elsema stocks pre-made loops for easy installation. Our pre-made loops are suitable for all types of installations.
Either for cut-in, concrete pour or direct hot asphalt overlay.
see
www.elsema.com/auto/loopdetector.htm
Detector position and installation
▪ Install the detector in a weatherproof housing.
▪ The detector should be as close to the sensing loop as possible.
▪ The detector should always be installed away from strong magnetic fields.
▪ Avoid running high voltage wires near the loop detectors.
▪ Do not install the detector on vibrating objects.
▪ When the control box is installed within 10 metres of the loop, normal wires can be used to connect the
control box to the loop. More than 10 metres requires the use of a 2 core shielded cable. Do not exceed 30
metres distance between control box and loop.
Dip-switch Settings
Feature
High Frequency
Low Frequency
Dip Switch settings
Frequency setting (Dip switch 1)
Dip switch 1 "ON"
Dip switch 1 "OFF"
Description
This setting is used in cases where two or more loop
detectors and sensing loops have been installed. (The
sensing loops and detectors should be positioned at least
2m apart). Set one detector to high frequency and the
other set to low frequency to minimize the effects of
cross-talk between the two systems.
2
ELSEMA
MD2010