1. PROGRAMMING SUMMARY
To enter the program mode, press the PGM button. The display shows (Pr)
when program mode is selected.
PGM
PROGRAM OPTION
NUMBER
P01
Mains Voltage Lower Limit
P02
Mains Voltage Upper Limit
P03
Generator Voltage Lower Limit
P04
Generator Voltage Upper Limit
P05
Frequency Lower Limit
P06
Frequency Upper Limit
P07
Frequency Delay Timer
P08
DC Supply Upper Limit
P09
Number of Start Attempts
P10
Wait before Start Timer
P11
Wait between Starts Timer
P12
Start Timer
P13
Stop Timer
P14
Mains Waiting Timer
P15
Cooling Timer
P16
Mains Contactor Timer
P17
Generator Contactor Timer
P18
Relay Configuration
Maintenance Period (engine
P19
hours)
P20
Maintenance Period (duration)
UNIT
Volt
Volt
Volt
Volt
Hz.
Hz.
Sec.
Volts
-
Sec.
Sec.
Sec.
Sec.
Min.
Min.
Sec.
Sec.
-
hours
months
- 3 -
FACT
MIN.
SET
VAL.
170
30
270
100
180
30
270
100
45
10
57
50
3
0
33.0
12.0
3
1
3
0
10
1
10
2
0
0
0.5
0
1.0
0
1
0
4
0
0
0
0
0
0
0
MAX.
VAL.
250
400
250
400
60
100
15
33.0
6
240
30
15
60
15
15
15
15
7
750
15