Elsist NEMO 2.0 400 사용자 설명서 - 페이지 8

{카테고리_이름} Elsist NEMO 2.0 400에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Elsist NEMO 2.0 400 11 페이지. Nemo2.0 series single- phase line interactive

Elsist NEMO 2.0 400 사용자 설명서
NEMO2.0 65 • 80 • 120 • 160 • 200 • 300 • 400
LINE INTERACTIVE
4. Mains OFF - UPS ON (DC Start)
Situation that occurs when the UPS is switched on
via the button on the front panel. After a long and
continuous beep, the display lights up as shown. The
batteries are feeding the load and are discharging. A
beep indicates the remaining autonomy, the more the
beep's frequency is higher the less the autonomy
time will be. When the battery reaches the end of
discharge level, then "6" icon will also start blinking.
5. Main ON - UPS ON (Overload)
Situation that occurs when a load higher than its
capability is connected to the UPS working in normal
mode. The icon "7" lights up until the load is above
the limits, and the two "7-8" icons blink simultaneously
with a continuous beep. After a few seconds, the UPS
move to protection mode and switches off. The load is
not supplied.
6. UPS error
Situation that occurs when the UPS detects a fault
such as a short circuit or a very high overload at the
output. The UPS switches off and the display shows
the icon "9" as in the figure, moreover you will hear a
continuous beep. To reset the beep, turn off the UPS
with the On/Off button on the front panel.
8 – TROUBLESHOOTING
STATUS
LCD display is Off
Continuous beep when Mains is
present
Battery autonomy time in back-up
mode is short
Battery mode icon is On but
Mains is present
Battery is not recharged
Rev. 02 27 Gennaio 2017
Discharged battery
Battery failed
On/Off button is not switched On
Overload on UPS
Overload on UPS
Battery voltage is very low
Battery failure due to high
ambient temperatures or
improper operation of the
battery
Power cord is not connected
Input fuse is blown
Input fuse is blown
NOTE: If there are other conditions not listed, then contact our service center.
CAUSE
SOLUTION
Recharge the battery for at least 8hr
Replace the battery with the same
type of product
Push ON/OFF button on front panel
Verify that load doesn't exceed the
rating of the UPS
Partially remove the load
Recharge the battery for at least 8hr
Replace the battery with the same
type of product
Check that power cord is correctly
plugged in.
Check the fuse in its housing on the
rear of UPS and replace it if blown.
Check the fuse in its housing on the
rear of UPS and replace it if blown.
8