E2 Serial Port Setup
1. Log into the E2 controller by pressing the
2. Enter USER in the Username field and press
3. Enter PASS in the Password field and press
4. Press
,
,
5. Press
twice to move to the C3: Serial tab.
6. Press
to highlight the COM2 Connection parameter.
6.a. Press
or MODBUS-3 connection).
6.b. Press
6.c. Set the MODBUS connection as follows:
(Press
• COM2 Baud: 19.2K Baud
• COM2 Data Size: 8
• COM2 Parity: None
• COM2 Stop Bits: 1
7. Press
to save changes.
8. Press
to go back to the Home screen.
Note: The XM MODBUS Connection must be set to 19.2K Baud.
Document Part # 026-4240 Rev 0 10-FEB-2015