Emerson Dixell 678D V.2.5 Quick Start Manual - Page 2
Browse online or download pdf Quick Start Manual for Measuring Instruments Emerson Dixell 678D V.2.5. Emerson Dixell 678D V.2.5 9 pages.
4. Press
to save changes.
5. To exit, press
flashing.
E2 Serial Port Setup
1. Log into the E2 controller by pressing the
2. Enter USER in the Username field and press
3. Enter PASS in the Password field and press
4. Press
,
,
5. Press
twice to move to the C3: Serial tab.
6. Press
to highlight the COM2 Connection parameter.
6.a. Press
or MODBUS-3 connection).
6.b. Press
6.c. Set the MODBUS connection as follows:
(Press
• COM2 Baud: 19.2K Baud
• COM2 Data Size: 8
• COM2 Parity: None
• COM2 Stop Bits: 1
7. Press
to save changes.
8. Press
to go back to the Home screen.
Note: The XM MODBUS Connection must be set to 19.2K Baud.
Document Part # 026-4240 Rev 0 10-FEB-2015
©2015 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
+
or wait for a few seconds without pressing any button; the display will start
,
(General Controller Info).
(LOOK UP) and select MODBUS-1 (if MODBUS-1 is being used, select MODBUS-2
to set the configuration.
to select options and
button.
.
.
Figure 3 - C3: Serial Tab
to set the configuration.)
Page 2 of 9