Reference Manual
00809‐0200‐xxxx, Rev AA
April 2010
Grounding
The Field Link enclosure should always be grounded in accordance with national and local electrical codes. The
most effective grounding method is a direct connection to earth ground with minimal impedance. Ground the
Field Link by connecting the external ground lug to earth ground. The connection should be 1 Ω or less.
STEP 2: Verify Operation
Add local display screens here.
Power‐Up Sequence
Upon applying power to the Field Link the LCD meter will activate and display a series of startup screen. The
following screens are displayed during startup.
1. Startup Screen 1 – All segments on
2. Startup Screen 2 – Device Identification
3. Startup Screen 3 – Tag
4. Startup Screen 4 – Status
Normal Operation
After the initial startup screens the Field Link will cycle through several periodic screens.
1. Electronics Temperature Screen
2. Percent Range Screen
3. Wired Interface Usage
4. Radio Interface Usage
The field link will continue to rotate through each periodic screen through the course of normal
operation. If any diagnostic or fault condition occurs, a corresponding diagnostics screen will appear.