Emerson FB2100 현장 교체 매뉴얼 - 페이지 4

{카테고리_이름} Emerson FB2100에 대한 현장 교체 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Emerson FB2100 16 페이지. Flow computer i/o terminal board
Emerson FB2100에 대해서도 마찬가지입니다: 현장 교체 매뉴얼 (16 페이지), 현장 교체 매뉴얼 (8 페이지), 현장 교체 매뉴얼 (14 페이지), 현장 교체 매뉴얼 (16 페이지)

Emerson FB2100 현장 교체 매뉴얼
FB2100/FB2200 Flow Computer Battery Field Replacement Guide
D301823X012
November 2020
WARNING
EXPLOSION HAZARD -Substitution of any components may impair suitability for Class I, Division
2.
WARNING
EXPLOSION HAZARD - Do not disconnect equipment unless power has been removed or the area
is known to be non-hazardous.
WARNING
EXPLOSION HAZARD – Do not replace batteries unless power has been switched off or the area is
known to be non-hazardous. Change batteries only in an area known to be non-hazardous.
Note
Use these cell batteries only in devices where the servicing of the cell circuit and replacement of the
lithium cells is done by a trained technician.
Removing/Replacing the Main Power Battery (Strap Holds Battery)
UL Listed Lead Acid Battery Field Installed Accessory Kit for Use in Class I, Division 2, Groups A, B, C,
and D.
WARNING
There are no user-serviceable parts inside the battery pack. Do not open the battery pack as you
may damage the battery pack or injure yourself.
Keep the replacement battery pack handy during the procedure.
1.
2
Flow Computer Lead Acid Battery Field Installed Accessory Kit Part No. 399285-01-0 for Use
with UL Listed Class I, Division 2, Groups A, B, C, & D Model Series FB2100 and FB2200
Remove the plastic tabs covering the connectors on the new battery pack.