Emerson FB2100 현장 교체 매뉴얼 - 페이지 11
{카테고리_이름} Emerson FB2100에 대한 현장 교체 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Emerson FB2100 16 페이지. Flow computer i/o terminal board
Emerson FB2100에 대해서도 마찬가지입니다: 현장 교체 매뉴얼 (16 페이지), 현장 교체 매뉴얼 (8 페이지), 현장 교체 매뉴얼 (14 페이지), 현장 교체 매뉴얼 (16 페이지)
FB2100/FB2200 Flow Computer I/O Termination Board Field Replacement Guide
Replacing Pluggable Terminal Blocks
Restrictions
Hazardous area approvals request that any part replaced in the field be the exact same part ("like-
for-like"). Upgrading or substituting different parts violates hazardous area certification.
Refer to the table below for the correct field replacement part number.
Item
Flow Computer Terminal Block Field Installed Accessory Kit for use
with UL Listed Model Series FB2100 and FB2200. 4-way terminal block
(in pack of 4):
UL Field Installed Accessory Kit for Use in Class I, Division 2, Groups A, B, C, D
Required Tools
1/8-inch flat-head screwdriver (for 5.08 mm pitch terminal block connections)
Ambient Temperature Ranges:
May be used up to a maximum ambient temperature of 80°C and a minimum ambient
temperature of –40°C; refer to the data plate attached to the device for ambient temperature.
WARNING
EXPLOSION HAZARD: Substitution of any components may impair suitability for Class I, Division
2.
WARNING
EXPLOSION HAZARD: Do not disconnect equipment unless power has been removed or the area
is known to the non-hazardous.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
D301805X012
November 2020
Field Replacement Kit
Part Number
395807010-KIT
9