AGS Merlin 1000Si 설치 및 운영 매뉴얼 - 페이지 7

{카테고리_이름} AGS Merlin 1000Si에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AGS Merlin 1000Si 16 페이지. Gas safety products, gas utility controller
AGS Merlin 1000Si에 대해서도 마찬가지입니다: 사용자 및 설치 매뉴얼 (7 페이지), 사용자 및 설치 매뉴얼 (9 페이지), 사용자 설명서 (12 페이지)

AGS Merlin 1000Si 설치 및 운영 매뉴얼
Installation & Operation Manual
Fire Panel Integration
The Merlin 1000Si can be integrated with a fire alarm to close the gas supply automatically in
the event of a fire. The volt free fire alarm signal can be wired in series with any remote
emergency shut off buttons.
If there are no remote emergency shut off buttons being installed, wire this directly to the
terminal marked [EM REMOTE].
Auto Shut-Down - Timeout Period
The system has an auto-shut down feature after a selected time.
There are two switches located on the circuit board labelled [TIME1] & [TIME2].
These can be configured to select the required timeout/ shut-down period.
TIME 1
TIME 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Note:
Upon timeout the gas supply will be turned off
1000Si IOM Rev: 06
Timeout Period
2 Hours (Default)
4 Hours
8 Hours
Disabled
01-20
Merlin 1000Si
7