DYNISCO PG500 Series
NOTE: Power supply (G115 option) can be operated with either
115 VAC or 230 VAC. Units shipped from the factor are preset to be
used with 115 VAC. To modify the input voltage to 230 VAC, refer
to the component layout in Figure 9.
115 VAC
Remove JU-3
Install JU-2 and JU-1
230 VAC
Remove JU-2 and JU-1
Install JU-3
FIG. 9
2.5

Alarm Manual/Automatic Reset Option

Units incorporating alarms are shipped set for automatic alarm: i.e.,
the alarm relay resets automatically when the pressure drops back
below the setpoint.
If manual reset is desired, remove the factory installed jumper
between terminals 4 and 5 (Reset) on the terminal block. Replace
jumper with a normally open pushbutton between the two terminals.
2.6

Alarm Hi/Low Modification (alarm units only)

Units equipped with alarms are adjustable to provide either a Hi or
Low alarm setting. Units shipped from the factory are set for "Hi"
alarm, i.e., alarm relay trips upon ascending pressure. To modify unit
for a low alarm, remove gauge face per Figure 5. Remove Jumper on
signal conditioning board and reinstall per Figure 10.
FIG. 10