Afore HNS2000TL 설치 매뉴얼 - 페이지 11

{카테고리_이름} Afore HNS2000TL에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Afore HNS2000TL 15 페이지.

 
4. Finally, insert the AC connection socket into the AC socket on the inverter audibly snaps into 
place. 
 
DANGER!
Danger to life due to high voltages in the inverter. 
• Do not switch on the circuit breaker until the PV generator has been connected and the inverter 
is securely closed. 
 
5.3 Connection of the PV Generator (DC) 
CAUTION!   
Load Disconnection Unit 
You must install an individual circuit breaker on the DC side out of each inverter, in order that the 
inverter can be safely installed. 
 
5.3.1 Conditions for the DC Connection 
• The connected PV modules must meet following requirements 
– Same type 
– Same number 
– Identical alignment 
– Identical tilt 
• The following limit values at the DC input of the inverter must not be exceeded (connecting to a 
higher voltage will destroy the device): 
Anyhome 
Maximum input voltage 
1.5KW 
500V 
2KW 
500V 
 
5.3.2 Assembling the DC Plug Connector 
In order to connect to the inverter, all connection cables of the PV modules must be equipped 
with the DC plug connectors provided. You will find the necessary DC plug connector for DC 
connection in the delivery. 
 
   
Maximum input current 
8A 
12A