4. Finally, insert the AC connection socket into the AC socket on the inverter audibly snaps into
place.
DANGER!
Danger to life due to high voltages in the inverter.
• Do not switch on the circuit breaker until the PV generator has been connected and the inverter
is securely closed.
5.3 Connection of the PV Generator (DC)
CAUTION!
Load Disconnection Unit
You must install an individual circuit breaker on the DC side out of each inverter, in order that the
inverter can be safely installed.
5.3.1 Conditions for the DC Connection
• The connected PV modules must meet following requirements
– Same type
– Same number
– Identical alignment
– Identical tilt
• The following limit values at the DC input of the inverter must not be exceeded (connecting to a
higher voltage will destroy the device):
Anyhome
Maximum input voltage
1.5KW
500V
2KW
500V
5.3.2 Assembling the DC Plug Connector
In order to connect to the inverter, all connection cables of the PV modules must be equipped
with the DC plug connectors provided. You will find the necessary DC plug connector for DC
connection in the delivery.
Maximum input current
8A
12A
9