ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Ventilation for the Inbuilt Heater Space
Pitched Roof with Ceiling Space
• The ceiling must have an opening around the 12" (300mm) flue
casing of a 350mm diameter hole, ie minimum of 25,529 mm2
evenly spaced around flue, i.e. a 25mm clearance around the
flue to combustible materials or equivalent.
• Ensure the roof space is ventilated, i.e. weep holes etc.
1/11/19