4 Specification

4.1 Approvals

PrimoBox ACB 910 mixing unit for condensing boilers
Table 1: Technical data of ACB 910 units
Parameter / part
General specification
Dimensions (W x H x D)
Weight
Circulation pump
Rotary mixing valve
Pressure
Heat source connections
Connection of individual zones
Heating medium temperature
Glycol concentration
Installation power
Water capacity
Supply voltage
Supply voltage
Power consumption
Housing protection
The PrimoBox ACB 910 mixing unit for condensing boilers is subject
to the Pressure Directive 2014/68 / EU and in accordance with art. 4.3
(sound engineering practice) are not CE marked.
The circulating pump provided with the product has a declaration
of conformity, which is available on the manufacturer's website.
The ARM ProClick electric actuator used in the ACB unit complies
with EU directives on LVD low voltage electrical equipment
(2014/35/EU) and EMC electromagnetic compatibility (2014/31/EU).
Value / Description
400 x 450 x 160mm
11,7 kg
Grundfos UPM 3 AUTO 15-70 130 mm
Kvs 3,6 with 3-point electric actuator
ARM ProClick 230 V
AC
max 4,5 bar
male G¾"
female G¾"
5°C ÷ 95°C
max 30%
max 26 kW
1 l
230 V AC ± 10%, 50 Hz
max 52 W
IPX 0
Instruction manual
50 Hz
11